Why the RCD trips when you switch the lights on

The whole group trips the RCD when switched on together, but not one at a time. Each driver contributes earth leakage current, and a simultaneous close adds a transient on top. Sizing formula for a 30 mA RCD, three ways to split the circuit, a six-step location procedure and four factors that make it worse.

Last updated:2026-11-02

On this page
  1. The one-sentence rule: design to one third of the rated residual current, not to the rating
  2. Where the leakage comes from: every unit contributes
  3. Computing how many units fit
  4. Why one at a time is fine but all at once trips: the transient layer
  5. Three ways to fix it, in order
  6. Four things that make it worse (check these before touching the board)
  7. Six steps to locate it
  8. Acceptance checklist

A whole group of luminaires trips the residual current device when switched on together but not one at a time. In most cases nothing is wrong with the drivers: every switched-mode supply contributes a small earth leakage current, and with enough units the sum matters - plus a transient on top when they all close at once. This article gives a size limit you can compute, three ways to fix it, and a six-step procedure to locate the cause.

The one-sentence rule: design to one third of the rated residual current, not to the rating

An RCD does not trip at one hard value. On a 30 mA type, it should not trip below about 15 mA (0.5 x I delta n) and should trip above 30 mA, with an uncertain band between. Design has to keep out of that band instead of sitting against 30 mA. Exact classes and types follow the device datasheet and local rules.

Where the leakage comes from: every unit contributes

A switched-mode supply has EMI suppression capacitors (X and Y) across its input and parasitic capacitance in the transformer primary, and together they form a small path to earth during normal operation. That current:

Computing how many units fit

n_max = (I_delta_n x 0.33) / I_leak_per

I_delta_n     rated residual operating current of the RCD (commonly 30 mA)
0.33          design factor, leaving room for transients and ageing
I_leak_per    leakage current of one driver (from the datasheet, typically 0.25 to 0.75 mA)

For a 30 mA RCD on a 230 V 50 Hz system:

Leakage per unitDesign limitReaching the 15 mA bandWhat it means on site
0.25 mAabout 40 units60 unitsSmall units, rarely a problem
0.50 mAabout 20 units30 unitsTypical band for mid-power constant-voltage units
0.75 mAabout 13 units20 unitsLarge units; whole-floor facades hit this first
1.00 mAabout 10 units15 unitsThe circuit must be split
The second column is the design figure; the third is only where it starts to get risky. Damp seasons and capacitor ageing eat the gap between them.
Leakage adds up with unit count: design to 10 mA, not 30 mA (30 mA RCD) 10 mA design limit 15 mA start of uncertain band 30 mA trip line 20 units 13 units 0.5 mA each 0.75 mA each 0 20 units 40 units 0 10 15 30 mA x axis: drivers on one RCD; y axis: total leakage; dots mark where each curve hits the design line
One parameter separates the two curves: 0.5 mA to 0.75 mA per unit drops the same circuit from 20 units to 13

Why one at a time is fine but all at once trips: the transient layer

Closing units one by one spreads the inrush over time. Closing them together means:

That is why the leakage meter reads low and the breaker still trips. The test is simple: if closing one at a time holds but closing the main trips, it is transient summation, not an insulation fault.

Three ways to fix it, in order

  1. Split the circuit (first choice): divide one RCD way into two or three, each inside the design limit. It costs a few modules in the board and it shrinks the failure zone - one way trips, the rest stay lit
  2. Get the real per-unit leakage and recount: ask the supplier for the measured leakage current in the datasheet and recompute with the 0.33 factor. Sometimes a lower-leakage model holds the existing circuit, which is cheaper than reworking the board
  3. Change the protection scheme: a time-delayed (selective) RCD upstream with ordinary RCDs or MCBs downstream, so only the layer nearest the fault trips. This is distribution design: it must be done by a licensed electrician to local rules, and it has to be confirmed that the higher rated residual current is permitted at that location
Swapping a 30 mA device for a 100 mA one is the easiest option and the last one you should take: it lowers personal protection and most local rules do not allow it. Try the first two first.

Four things that make it worse (check these before touching the board)

  1. Neutral and earth crossed or earthed twice: part of the working current returns through earth and the residual current is artificially raised
  2. Driver cases bonded to large metalwork: luminaires or trunking increase parasitic capacitance to earth; an insulating shim helps
  3. Long output cable run against earth or metal: same effect, very visible on outdoor facades
  4. Insulation drop in the damp season: rainy seasons and condensing basements are the peak season for nuisance tripping; readings fall again once dry - design for the worst season, do not accept on a dry day

Six steps to locate it

  1. Tell leakage from overcurrent: RCD only, MCB holding means leakage; both tripping or the MCB alone is an inrush current and breaker sizing problem
  2. Close one way at a time: find which way, shrinking the search from a whole floor to one circuit
  3. Clamp the residual current: clamp line and neutral together on a single-phase circuit; the reading is the residual current. Compare against the 10 mA design value
  4. Halve the load: disconnect half, close again, and narrow down each round
  5. Inspect wiring and mounting: neutral and earth crossed, case bonded to metalwork, output cable routing
  6. Get the datasheet figure and recount: with the real leakage current, decide between splitting the circuit and changing the model

Acceptance checklist

  1. Per-unit leakage taken from the datasheet, not estimated
  2. Units per RCD way at or below (I delta n x 0.33) divided by per-unit leakage
  3. Main switch closed three times, no trip
  4. Residual current re-measured in the damp season, or after a water test, still 15 mA or less
  5. A trip affects only that way, not the whole floor
  6. The final protection type and rating comply with local rules, with a signed record from the electrician

Leakage figures for constant-voltage units H01, K01 and S01 and constant-current unit H19 must come from their own datasheets. Circuit current and power conversion runs through the LED driver sizing calculator, and outdoor or damp locations add the condensation and insulation requirements in IP rating and outdoor selection.

The 0.25 to 0.75 mA range here is a typical order of magnitude, not a commitment for any specific model. Selection and modification of distribution and protective devices must follow local rules and the latest requirements of the certifying body, carried out by a licensed electrician.
Send us the number of units on the circuit, the wattage per unit, the RCD type and its rated residual current. We will compute how many units the circuit can carry, say whether to split or to change the protection, and write it up for your electrician. Contact →