Selection & sizing
Steady-state current is a quarter of the breaker rating and the circuit still trips on switch-on. This guide gives the comparison rule between inrush peak and the breaker magnetic trip threshold, the B/C/D curve conversion, a worked 16 A type C example, plus on-site measurement and an acceptance checklist.
Steady-state current sits at a quarter of the breaker rating and the circuit still trips the moment you switch it on. That is not an undersized breaker and it is not a faulty driver. What trips a breaker is the inrush of the first few milliseconds, not the running current. Once you put a number on it, circuit counts stop being guesswork.
N_max = (k x I_n) / I_peak
k lower bound of the breaker magnetic trip band (B 3, C 5, D 10)
I_n breaker rated current (A)
I_peak cold-start inrush peak of one driver (A)
Use the lower bound. The upper bound is where it might not trip; the lower bound is where it will not trip.
Topology moves the peak a long way: units with an NTC limiter or soft start can sit at 5-15 times running current, while unprotected designs reach tens of times. Always read the test conditions next to the published inrush figure - voltage, phase angle, cold or hot state.
Running current is what governs long-term heating, not tripping:
I = P / (U x PF)
e.g. 100 W, 230 V, PF 0.95 -> I about 0.46 A
| Step | Calculation | Result |
|---|---|---|
| Breaker magnetic threshold | 5 x 16 A | 80 A |
| Running current per unit | 100 / (230 x 0.95) | 0.46 A |
| Cold-start peak per unit | from the datasheet | 40 A |
| Units allowed to start together | 80 / 40 | 2 |
| Peak of four starting together | 4 x 40 | 160 A - above 80 A, trips |
| Running total of four | 4 x 0.46 | 1.83 A, only 11% of rating |
That is the counter-intuitive part: 11% of rating and it still trips. Published guidance for comparable mid- to high-power drivers quotes 2 units on a 16 A/230 V type B circuit and 3 units on type C (check the current manufacturer datasheet), which lands in the same range as the formula - a useful cross-check.
Magnetic trip bands are conventionally B 3-5x In, C 5-10x In and D 10-20x In under IEC 60898-1 (check the actual product data and local rules). The lower bound is the k in the formula:
| Curve | Magnetic band | 16 A threshold (lower bound) | Typical use |
|---|---|---|---|
| B | 3-5 x In | 48 A | Resistive, small lighting circuits |
| C | 5-10 x In | 80 A | General purpose, some inductive load |
| D | 10-20 x In | 160 A | Transformers, high inrush equipment |
Simplest: switch the full circuit on ten times from cold and note whether it trips, and on which attempt. A single trip means the margin is gone.
Quantitative: put a low-value shunt resistor in series (size the resistance and power rating for the circuit current and keep a safe working distance) and convert the scope voltage drop to current, or use a clamp meter with peak-hold (inrush) and convert per the instrument manual. Record four things: single-unit peak, N-unit peak, whether it tripped, and the breaker model and curve.
I = P / (U x PF)N_max = (k x I_n) / I_peak with the lower bound of k and round downDeciding circuit counts at specification stage is far cheaper than fixing it on site. High-power units in the H series such as H01 and H19, and K01 in the K series, all go through the same formula - do not estimate circuit counts from running power, because that number is optimistic in a dangerous way. Check power and current conversions with the LED driver sizing calculator; for DC-side cable size and voltage drop see the 12 V/24 V voltage drop and cable size table, and for other causes of flicker after switch-on see the LED flicker troubleshooting guide.
© 2026 YFX. Figures are for selection purposes. Always follow the datasheet and local wiring regulations for final installation.