The minimum load of a leading-edge triac dimmer is not a driver capability - it is the dimmer's holding-current requirement. This guide gives the current magnitudes, four reasons published figures fail in the field, a three-step on-site test, and how to size a dummy load.

Last updated:2026-10-31

On this page
  1. The one-sentence answer
  2. The mechanism: holding current is the real threshold
  3. Why the published figure collapses on site
  4. Three-step on-site test
  5. Common mistakes
  6. Acceptance checklist

"This driver has a 10 W minimum load" is misused about nine times out of ten. Minimum load is not a driver parameter. It is the smallest current the dimmer needs to stay conducting. Change the dimmer and the same driver can go from dimming to 5% to dropping out at 30%.

The one-sentence answer

Fix the order of investigation: check the dimmer's holding current first, then the driver's bleeder and bleeder capacity, and only then the driver's published dimming range. Reverse the order and you will keep swapping drivers while the problem sits in the wall.

The mechanism: holding current is the real threshold

A triac is a semi-controlled device. Once triggered it stays on only while load current remains above its holding current (I_H). Drop below that and it switches off part-way through the half cycle, then re-triggers on the next one - which shows up as low-end flicker, stepping, or the light simply going out.

Common wallbox leading-edge dimmers sit in the 20-70 mA range. Professional dimmer racks demand more; the figure quoted in theatre engineering discussions is around 100 mA. A single 12 W LED driver on 230 V at PF 0.9 draws roughly:

I = P / (U x PF) = 12 / (230 x 0.9) = 0.058 A, about 58 mA

So one 12 W driver already sits in the critical band of some dimmers. That is why a driver advertised with a "10 W minimum load" still flickers on certain wall units.

Load current versus holding current (one half cycle at 50 Hz, schematic) I_H holding current Peak well above I_H - conducts normally I_H Peak below I_H → drops out → flicker Leading edge: the dimmer removes the start of every half cycle firing point The smaller the conduction angle, the less time current has to rise - which is why deep dimming flickers most
Top: load current against holding current. Bottom: leading-edge chopping and conduction angle

Why the published figure collapses on site

CausePublished conditionReal conditionConsequence
Holding current not statedMeasured on an ideal dimmerReal dimmer I_H 20-70 mASame driver: 5% on one unit, 30% on another
Single load too small"10 W minimum"One 12 W unit on the circuitAbout 58 mA - right in the critical band
Capacitive inputTested as a resistive loadLED drivers are rectifier plus bulk capDistorted current after firing, easy misfire
Parallel maskingOne unit testedEight units on a circuitTotal current is fine, but individual units are not
Paralleling fixtures makes dimming look "better" because the total current clears the holding threshold - not because anything changed inside the driver. Test units one at a time. Testing only the whole circuit hides every weak unit.

Three-step on-site test

No special instruments needed beyond a clamp meter and the dimmer actually specified for the job.

Step 1 - sweep one unit

Connect a single driver to the real dimmer and ramp down slowly from 100%. Record three points:

Flicker above 20% points to holding current or curve mismatch, not a faulty driver.

Step 2 - add a dummy load

Put a resistive dummy load across the circuit, then repeat step 1. If the flicker point moves clearly down or disappears, the cause is confirmed: the circuit current is not enough to hold conduction.

Size the load from the current you need to add:

R = U squared / P      e.g. 230 V, 5 W  ->  R about 10.6 kohm
I = P / U              e.g. 230 V, 5 W  ->  I about 22 mA

In practice 5-10 W of resistive load is the usual starting point; theatre installations have long used a 40 W tubular heater as a dummy load, mounted where it cannot spill light. More power works better, but it costs energy whenever the circuit is live - a 5 W load left on all year is roughly 44 kWh, and the client should hear that number up front.

Step 3 - swap to a trailing-edge (ELV) dimmer

Repeat step 1 with the same driver on a trailing-edge dimmer. If trailing edge ramps smoothly below 5% while leading edge cannot, the verdict is clear: it is a topology mismatch, and changing drivers will not fix it.

Three steps separate "driver problem" from "dimmer problem". Most complaints about a driver "not dimming properly" are reclassified after step 3.

Common mistakes

Acceptance checklist

  1. Record the dimmer model and its stated holding current; if it is not published, design conservatively for 20-70 mA
  2. Work out the minimum circuit current: I = total P / (U x PF), compare with holding current and keep a 1.5 factor
  3. Sweep each unit individually and record flicker, step and dropout points in the acceptance sheet
  4. If flicker starts above 20%, retest with a dummy load before deciding to change the dimmer
  5. Run the trailing-edge comparison to settle topology versus driver
  6. Re-run step 3 whenever fixtures are added to the circuit

Deciding circuit count and per-unit wattage at design stage is far cheaper than adding dummy loads later. H01 and H19 in the H series and K01 in the K series are all specified for triac dimming, but compatibility is not a promise of identical dimming depth on every dimmer - confirm the dimmer model at the same time. For the differences between dimming methods see the dimming comparison table, and for other causes of low-end flicker see the LED flicker troubleshooting guide.

Cannot dim to the bottom, or flickering at low end? Tell us the dimmer model, the number of fixtures per circuit and the wattage of each - we will tell you whether it is holding current or the dimming curve, and point you to triac-compatible models. Contact →